Function description | Specification |
Rated input voltage (V) | 1PH 220V(-15%)~240V(+10%) 3PH 200V(-15%)~240V(+10%) 3PH 380V(-15%)~440V(+10%) |
Rated input frequency (Hz) | 50Hz or 60Hz, permissible range: 47~63Hz |
Rated output voltage (V) | Equal to input voltage with less than 5% error |
Rated output frequency (Hz) | 50Hz/60Hz, fluctuation range: ±5% |
Control mode | V/f control |
Max output frequency | 400Hz |
Speed ratio | 1:100 |
Overload capacity | 1m for 150% of rated current, 10s for 180% of rated current, 1s for 200% of rated current |
Analog input resolution | No more than 20mV |
Analog I/O | Input one 0~10V or 0~20mA, output one 0~10V or 0~20mA |
Digital I/O | Five normal inputs, one Y terminal output (in common use with normal digital output) and one programmable relay output |
Communciation | 485 communication MODBUS |
Installation mode | Wall installation |
Ambient temp | ﹣10~50℃, derated if the ambient temp is above 40℃ |
Cooling mode | 1PH/3PH 230V 0.2~0.75KW natural cooling |
1PH/3PH 220V 1.5~2.2KW, 3PH 380V 0.75~2.2KW air cooling | |
Fault protection | Provide dozens of fault protection functions: overcurrent, overvoltage, undervoltage, overtemp and overload |
Brake unit | Built-in brake unit in standard configuration |